Honeywell TH8110U Touch Screen Programmable Thermostats
APPLICATION
The TH8110U Universal Programmable Thermostats provide electronic control of 24 Vac heating and cooling systems or 750 mV heating systems. See Table 1 for a general description.
Table 1. TH811 Thermostats Description.
Model |
Power Method |
Changeover |
System Selection |
Fan Selection |
Comments |
TH8110U | Batteries or common wire | Automatic or manual selectable | Heat-Off-Cool-Auto | On-Auto-Circ | System and Fan selection vary based on system type |
INSTALLATION
When Installing this Product…
- Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
- Check ratings given in instructions and on the product to ensure the product is suitable for your application.
- The installer must be a trained, experienced service technician.
- After installation is complete, check out product operation as provided in these instructions.
CAUTION
Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment circuitry.
Disconnect the power supply before installation.
Selecting Location
Select a location for the thermostat about 5 ft (1.5m) above the floor in an area with good air circulation at an average temperature. See Fig. 1.
Do not install the thermostat where it can be affected by:
- Drafts or dead spots behind doors and in corners.
- Hot or cold air from ducts.
- Radiant heat from sun or appliances.
- Concealed pipes and chimneys.
- Unheated (uncooled) areas such as an outside wall behind the thermostat.
Installing Wallplate
CAUTION
Electrical Hazard.
Can cause electrical shock or equipment damage.
Disconnect power before wiring.
The thermostat can be mounted horizontally on the wall or on a 4 in. x 2 in. (101.6 mm x 50.8 mm) wiring box.
- Position and level the wallplate (for appearance only).
- Use a pencil to mark the mounting holes.
- Remove the wallplate from the wall and, if drywall, drill two 3/16-in. holes in the wall, as marked. For firmer material such as plaster, drill two 7/32-in. holes. Gently tap anchors (provided) into the drilled holes until flush with the wall.
- Position the wallplate over the holes, pulling wires through the wiring opening. See Fig. 2.
- Insert the mounting screws into the holes and tighten them.
WIRING (FIG. 5-11)
All wiring must comply with local electrical codes and ordinances.
- Select set of terminal identifications (Table 2) that corresponds with system type (conventional or heat pump) in Fig. 3.
- Loosen the screws for the appropriate system type selected; see Table 2. Insert wires in the terminal block under the loosened screw. See Fig. 4.
- Securely tighten each screw.
- Push excess wire back into the hole.
- Plug the hole with nonflammable insulation to prevent drafts from affecting the thermostat.
Table 2. Selecting Terminal Identifications for System Type.System Type
Wallplate Terminal Identifications Wiring Diagram reference
Standard Heat/Cool Conventional 5, 6 Heat Only Conventional 7 Heat Only with Fan Conventional 8 Heat Only Series 20 Conventional 9 Cool Only Conventional 10 Heat Pump with No Auxiliary Heat Heat Pump 11
Powering the Thermostat
There are two different ways to power the thermostat:
- Batteries (three AAA alkaline).
- 24 Vac Common wire.
Wiring 24 Vac Common
Wire the common side of the transformer to the C screw of the thermostat wallplate. When installing in a single transformer system, keep the jumper wire between the R and Rc screws. When installed in a two-transformer system, use the common from the cooling transformer to connect to C screw and remove the jumper wire between the R and Rc screws.
Inserting Batteries (Optional)
If not using a 24 Vac Common to power the thermostat, install three AAA alkaline batteries (included) in the back of the thermostat. Make sure the positive and negative terminals are oriented correctly, as marked on the device. See Fig.12.
Mounting the Thermostat
- Align the terminal screw blocks with the pins on the back of the thermostat.
- Push the thermostat straight onto the wallplate. See Fig. 13.
Adjusting Real-Time Clock
Setting Calendar and Time
Locate and remove the tab labeled Remove in the lower left corner on the thermostat back. The tab must be removed to activate the real-time clock. See Fig. 14.
This thermostat is designed to automatically keep the current time and day in memory for up to ten years under normal use after the calendar is set. When the thermostat is first powered, the display is ready to enter the calendar date (Fig.15).
IMPORTANT
The tab on back of the thermostat in the lower-left corner must be removed to activate this feature.
Using the Thermostat
The thermostat has a touchscreen interface. Words or symbols appear, highlighting keys, as needed, to complete tasks. Press keys with your fingertips. Sharp tips on pens or pencils can damage a thermostat.
- Use arrow keys to set Year, Month and Day (see Fig. 15).
- Press the Done key.
- Use arrow keys to set the current time. See Fig. 15.
- Press the Done key.
OPERATION
System and Fan Settings
The System default setting is Heat and the Fan default setting is Auto.
SYSTEM Settings
- Heat: The thermostat controls the heating system.
- Off: Both heating and cooling are off.
- Cool: The thermostat controls the cooling system.
- Auto: The thermostat automatically changes between heating and cooling systems, depending on indoor temperature. (See Installer Setup section.)
- FAN Settings
The Fan setting can be programmed into the thermostat schedule for each period (Wake, Leave, Return, Sleep). See the Owners Guide for additional information. - Preprogrammed Settings
Table 3 shows the default program settings. See the Owners Guide for complete instructions on changing the program.
Table 3. Default Program Settings.
Schedule Period |
Time |
Setpoints | Fan Setting | |
Heat | Cool | |||
Wake | 6:00AM | 70°F (21°C) | 78°F (25.5°C) | Auto |
Leave | 8:00 AM | 62°F (16.5°C) | 85°F (29.5°C) | Auto |
Return | 6:00 PM | 70°F (21°C) | 78°F (25.5°C) | Auto |
Sleep | 10:00 PM | 62°F (16.5°C) | 82°F (28°C) | Auto |
INSTALLER SETUP
This Universal Thermostat works with many different system types. To operate correctly, the thermostat must be set up to operate the installed heating and/or cooling system.
Installer Setup Menus
- Main Menu: Offers the most commonly used options. It is necessary to enter this menu to set the thermostat to the type of system it is operating. Many applications use only the Main Menu.
- Regional Menu: Offers choices often changed due to a particular area or region. For example, temperature display in Fahrenheit or Celsius is offered in this menu.
- Advanced Settings Menu: Offers more settings to fully customize the thermostat. Many of these settings do not require changing from the factory settings.
Entering Installer Setup
- The thermostat must be powered either with Alkaline AAA batteries or with 24 Vac Common wire.
- From the home screen, press System key. (Press Done or Cancel key to return to the home screen.)
- Five blank touch keys show on the bottom of the screen between the Done and Cancel keys. Press and holds the two blank keys on either side of the center blank key for approximately five seconds until the screen changes. See Fig. 16.
- The Installer Setup Number is displayed in the lower left. It is a four-digit code beginning with zero. The factory setting or other choice selection is displayed in the lower right. See Fig. 17. This is a two-digit code shown in the Options column of Table 4.
Changing Installer Setup Selections
- Advance to the next Installer Setup Number by pressing the up and down arrow keys to the right of the four-digit Installer Setup Number. See Fig. 17.
- Change the factory Setting Options by pressing the up and down arrow keys right of the two-digit code selection. See Fig. 17.
Exiting Installer Setup
- Press Done key to exit Installer Setup screen.
IMPORTANT
The three Installer Setup Menus (Tables 4-6) show all available options. These options customize themselves as you make selections to Installer Setup. So not all Installer Setup Selections are shown or are available to change.
Table 4. Main Installer Setup Menu.
Select |
Installer Setup Number |
Factory Setting | Other Choices |
Comments |
||
Option |
Description |
Options |
Description |
|||
Not used. | 1 thru 0099 | – | – | – | – | – |
Date (Year Upper) | 0120 | 20 | Set the first two digits of the current calendar year (20 for the year 2005, etc) | 21 | 21 -first two digits of the current calendar year (21xx) | 2000 -2178
available |
Date (Year Lower) | 0130 | 04 | Represents the last two digits of the current calendar year (2004). | 00 -99 | Select last two digits of the current calendar year. | 2001-2178
available |
Date (Month) | 0140 | 6 | Digit(s) represents the current calendar month. | 1-12 | The select number represents the current calendar month. | – |
Date (Day) | 0150 | 15 | Digit(s) represents the current calendar date. | 1-31 | Select the number that represents the current calendar date. | – |
Schedule Options | 0160 | 4 | 7-day programming | 0 | 0 -nonprogrammable | – |
System Type Selection | 0170 | 1 | 1 Heat/1 Cool Conventional System | 1-6 | 1-1 heat/1 cool
2- single-stage heat pump (no aux. heat) 3- heat only (no fan) 4 -heat only (with fan) 5-hot water Series 20 (3-wire or normally open zone valves) 6-cool only |
Available options and defaults vary by a thermostat.
System selection automatically modifies some default settings and/or hides other Installer Setup options. |
Fan Operation | 0180 | 0 | Conventional applications where equipment controls fan operation in heat mode. | 1 | A heat pump or electric heat application where thermostat controls fan operation in heat mode. | Only shown if the conventional system is selected. If the heat pump is chosen, the fan defaults to electric. |
Reversing Valve (O/B) Operation | 0190 | 0 | The O/B terminal is energized for reversing the valve in cooling | 1 | O/B terminal is energized for reversing the valve in heating | Only shown if the heat pump system is chosen. |
Select |
Installer Setup Number |
Factory Setting | Other Choices |
Comments |
||
Option |
Description |
Options |
Description |
|||
Cycles per hour (mph) for 1st Stage Compressor | 0220 | 3 | Compressor Stage 1 cycles per hour (mph) | 1-6 | 1-6 available;
3 is recommended. |
– |
Cycles per hour (mph) for 1st Stage Conventional Heat | 0240 | 5 | Conventional Heat Stage 1 cycles per hour (mph) | 1-12 | 1-12 available; typical settings:
1-1 kph used for steam or gravity system. 3-3 kph used for hot water systems or high efficiency (90% or better) fossil fuel forced-air systems. 5-5 kph used for standard fossil fuel-forced air systems. 9-9 kph used for electric forced air heat systems. |
Not shown if the system selection is a heat pump.
Selection in this stage changes the default cph for 2nd stage heat. |
Continuous Backlight | 0280 | 0 | Backlight not on continuously.
The thermostat backlight comes on with each keypress. |
1 | Backlight is on continuously (the thermostat must have a common wire attached for this function). | Option is always shown; however, continuously on backlight works only if the thermostat is wired with 24 vacs Common. |
Additional Menu Choices | 0290 | 0 | Only the main menu options are shown. Installer Test Options are shown next (Table 7). | 1,2 | 1- Main Menu and Regional Settings are shown plus Installer Test (Tables 5 and 7 only).
2- All remaining Menu/ Options shown plus Installer Test (Tables 5, 6, and 7). |
The majority of applications require only the Main Menu Options. |
Table 5. Regional Settings Menu.
Select |
Installer Setup Number | Factory Setting | Other Choices |
Comments |
||
Option | Description | Options | Description | |||
Changeover | 0300 | 0 | Manual changeover | 1 | 1-auto changeover | – |
Deadband | 0310 | 3 | Heating and cooling setpoints can be set no closer than 3°F (1.5°C) | 2 thru 9 | Heating and cooling setpoints can be set no closer than chosen value:
2-2°F(1°C) 3-3°F(2°C) 4-4°F(2.5°C) 5-5°F(3°C) 6-6°F(3.5°C) 7-7°F(4°C) 8-8°F(4.5°C) 9-9°F (5°C) |
Shown only if the automatic changeover is selected. |
Temperature Indication Scale | 0320 | 0 | Temperature is displayed in °F. | 1 | Temperature is displayed in °C. | – |
Daylight Savings | 0330 | 1 | Daylight savings enabled (United States). | 0 | 0-daylight savings is disabled. | Set to 0 in areas that do not follow daylight savings. |
Remote Temperature Sensor (Outdoor or Indoor) | 0340 | 0 | No remote temperature sensor | 1,3 | 1 outdoor temperature sensor for display only.
3-indoor temperature sensor |
Defaults and Options depend on System Type selected. Indoor Temperature Sensor uses an averaging network and does not include an onboard sensor. |
Table 6. Advanced Settings Menu.
Select |
Installer Setup Number | Factory Setting | Other Choices |
Comments |
||
Option | Description | Options | Description | |||
Furnace Filter Change Reminder | 0500 | 0 | Furnace filter change reminder off | 1-6 | 1-10runtimedays 2-30runtimedays 3-60runtimedays 4-90runtimedays 5-120runtimedays 6-365runtimedays | Run time based on call for the fan. |
Humidifier Pad Replacement Reminder | 0510 | 0 | Humidifier pad replacement reminder off | 1-3 | 1-90calendardays 2-180calendardays 3-365calendardays | – |
UV Lamp Replacement Reminder | 0520 | 0 | UV Lamp replacement reminder off | 1 | 1-365 calendar days | – |
Adaptive Intelligent Recovery™ | 0530 | 1 | Adaptive Intelligent Recovery™ control is activated (the system starts early so the setpoint is reached by the start of the program period). | 0 | 0-conventional recovery (system starts recovery at the programmed time) | – |
Number of Periods | 0540 | 4 | Four periods available (Wake, Leave, Return, Sleep) | 2 | Two periods available (Wake and Sleep) | Not shown in non-programmable is selected. 2 or 4 applies to all days of the week. |
Minimum Compressor Off Time | 0580 | 5 | Five-minute minimum off time for compressor | 0, 2, 3, 4 | Minimum number of minutes the compressor is off between calls for the compressor | – |
Heat Temperature Range Stop | 0600 | 90 | Highest heating setpoint. | 40 to 89 | Temperature range (1°F increments) of heating setpoint. | Shown in 1/2 °C. |
Cool Temperature Range Stop | 0610 | 50 | Lowest cooling setpoint. | 51 to 99 | Temperature range (1°F increments) of cooling setpoint. | Shown in 1/2 °C. |
Clock Format | 0640 | 12 | 12-hour clock format | 24 | 24-hour clock format | – |
Extended Fan on time Heat | 0650 | 0 | No extended fan operation after calling for heat ends | 90 | Fan operation is extended 90 seconds after calling for heat ends. | Not shown if fan operation is set to fossil fuel or in Cool Only Systems |
Extended Fan on time Cool | 0660 | 0 | No extended fan operation after calling for cool ends | 90 | Fan operation is extended 90 seconds after calling for cool ends. | Not shown in Heat Only Systems. |
Select |
Installer Setup Number | Factory Setting | Other Choices |
Comments |
||
Option | Description | Options | Description | |||
keypad Lockout | 0670 | 0 | Unlocked keypad | 1, 2 | 1- partially locked keypad
2- fully locked keypad |
Unlocked-all functions are available.
Partially locked- only temperature up and down keys and the ability to enter and modify Installer Setup mode are available. A fully locked-only ability to enter and modify Installer Setup mode is available. |
Temperature Control in Heat | 0680 | 2 | Standard temperature control in heating | 1, 3 | 1-less aggressive temperature control (could cause the temperature to undershoot)
3-more aggressive temperature control (could cause temperature overshoot) |
Applies to the recovery ramp and the use of auxiliary heat during recovery.
Choose 1 if getting temperature overshoot.
Choose 3 if getting the temperature to undershoot. |
Temperature Control in Cool | 0690 | 2 | Standard temperature control in cooling | 1, 3 | 1-less aggressive temperature control (could cause the temperature to undershoot)
3-more aggressive temperature control (could cause temperature overshoot) |
Applies to the recovery ramp.
Choose 1 if getting temperature overshoot.
Choose 3 if getting temperature to undershoot. |
Temperature Display Offset | 0700 | 0 | No difference in displayed temperature and actual room temperature | -3, -2, -1,
0, 1, 2, 3 |
-3°F(-1.5°C)
-2°F(-1°C) -1°F(-.5°C) 0 F(0.°C) 1°F(.5°C) 2°F (1°C) 3°F (1.5°C) |
– |
Reset Thermostat | 0710 | 0 | No thermostat reset. | 1 | Resets all Installer Setup Options to default values and resets schedule to default setting. | Only calendar settings and time are retained. |
SYSTEM CHECKOUT
Installer System Test
The Installer System Test mode is used to test the HVAC system(s). See Table 7. While in System Test mode, minimum off-time for compressors is bypassed. The Installer Test is part of the Installer Setup options. Enter the Installer Setup screen and press the Down arrow key to bring up test selection(s) quickly. See Fig. 16.
ADVANCED FEATURES
Outdoor or Indoor Temperature Sensor
Allow outdoor or indoor temperature sensors to absorb the air for a minimum of five minutes before taking a reading.
See the Sensor instructions for more information.
CAUTION
Equipment Damage Hazard.
Minimum compressor off-time is bypassed during Installer System Test.
Avoid cycling the compressor quickly
Table 7. System Test
Select |
Installer Setup Number | Factory Setting | Other Choices |
Comments |
||
Options | Description | Options | Description | |||
Installer Test Cool | Test 1 | 0 | Cool is off | 1 | 0- cool off
1- cool stage 1 turns on |
System selection determines tests available and the number of stages shown. |
Installer Test Fan | Test 2 | 0 | Fan is off | 1 | 0- fan off
1- fan turns on |
|
Installer Test Heat | Test 3 | 0 | Heat is off | 1 | 0- heat off
1- stage 1heat on |
TROUBLESHOOTING
Symptom | Possible Cause | Action |
The display does not come on. | The thermostat is not being powered. | Check for 24 Vac between C and Rc.
Verify AAA batteries are installed correctly and well. |
Temperature settings do not change. | The upper or lower temperature limits were reached. | Check temperature setpoints.
Check Installer Setup Numbers 0600 and 0610; modify. |
The keypad is fully locked. | Check Installer Setup Number 0670 to change keypad lock options. | |
The heating or cooling does not come on. | The thermostat minimum off-time is activated. | Wait up to five minutes for the system to respond. |
System selection is not set to Heat or Cool. | Set system Selection to the correct position. | |
The O/B terminal is not set correctly (Heat Pumps only). | Check Installer Setup Number 0190 and set it correctly. | |
System type Selection is incorrect. | Check Installer Setup Number 0170 and make sure the correct System type is chosen. | |
The thermostat is calling for Heat (Heat on) or Cool (Cool on) but no heating or cooling is running. | The heating or cooling equipment is not operating. | Check to wire.
Check Installer Setup Number 0170; verify correct system type is chosen. Verify equipment operation in System Test mode. |
The thermostat does not respond when the touchpad is pressed. | The keypad is locked. | Check Installer Setup Number 0670 to change keypad locked options. |
REFERENCE:
Download Manual:
Honeywell TH8110U Touch Screen Programmable Thermostats Installation Guide
Honeywell TH8110U Touch Screen Programmable Thermostats Installation Guide
The post Honeywell TH8110U Touch Screen Programmable Thermostats Installation Guide appeared first on thermostat.guide.
source https://thermostat.guide/honeywell/honeywell-th8110u-touch-screen-programmable-thermostats-installation-guide/
No comments:
Post a Comment