Sunday, 29 January 2023

Trane TCONT900 COMFORT CONTROL Thermostats Installation GUIDE

TRANE-LOGO

Trane TCONT900 COMFORT CONTROL Thermostats

Trane-TCONT900-COMFORT-CONTROL-Thermostats-Installation-GUIDE-product

ALL phases of this installation must comply with NATIONAL, STATE, AND LOCAL CODES
NOTE: If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Dispose of it properly.
NOTE: Contact your local waste management authority for instructions regarding recycling and the proper disposal of an old control.

INTRODUCTION

The TCONT900AC43UA is a communicating programmable Comfort Control that supports single-stage or multi-stage heat/cool and heat pump applications. It is a wall-mounted, low voltage (24VAC) communicating Comfort Control with a backlit LCD and a touch screen display. Room temperature is maintained by controlling the operation of heating, cooling, heat pump, and dual fuel systems via digital, 2-way communications. The Comfort Control will communicate with and identify all ComfortLinkTM II components in the system. It is easily manually configured via the user-friendly Installer Setup menu. The Comfort Control features include separate heating and cooling setpoints, selectable auto or manual changeover, menu-driven 7-day programming, adjustable filter reminders, and outdoor temperature sensing. Setup selections and diagnostics are stored indefinitely in the Comfort Control’s nonvolatile memory eliminating the need for battery backup.

Table 1. TCONT900AC43UA Comfort Control

 

Power Method

 

Changeover

System Selection and Fan Keys*  

Fan Selection

 

Comments

24 Vac common wire Automatic or Manual selectable Heat-Off-Cool-Auto Emergency Heat On-Auto-Circ System and Fan selection vary, based on system type
Humidity sensor to control dehumidification and humidification

See the System and Fan Keys section for specific information.

Accessories

Optional
BAYSEN01ATEMPA – Outdoor Sensor – For use with communicating outdoor equipment BAYTAM00AC00UA – Telephone Access Module (TAM)

PRODUCT SPECIFICATIONS

  •  Power Source:  18-30 VAC, Class II, 50/60Hz
  • Storage Range: -30°F-150°F (-34.4°C-65.6°C), 5%-90% RH non-condensing
  • Operating Temperature Range: 0°F-120°F (-17.8°C-37.2°C), 5%-90% RH non-condensing
  • System Mode: Heat, Cool, Auto, Emergency Heat, and Off
  • Fan Mode: On, Auto, and Circ
  • Cooling Setpoint Temperature Range: 60°F-99°F (15.5°C-37.0°C), 1°F (0.5°C) resolution
  • Heating Setpoint Temperature Range: 50°F-90°F (10°C-32.0°C), 1°F (0.5°C) resolution
  • Indoor Temperature Display Range:         40°F-99°F (4.5°C-37.0°C)Outdoor Temperature
  • Display Range:    -40°F-127°F (-40°C-53.0°C) Indoor
  • Humidity Display Range:      0%-99%, 1% resolution
  • Minimum Cycle Off Time Delay:   Compressor: 5 minutes
  • Heat: 0 minutes

This comfort control contains a Lithium battery which may contain Perchlorate material. Due to State Law in California, the following statement is required: chlorate Material – special handling may apply. See www.dtsc.ca.gov/hazardouswaste/perchlorate

INSTALLATION

When Installing this Product…

  1. Read these instructions carefully. Failure to follow these instructions can damage the product or cause a hazardous
  2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your
  3. Installer must be a trained, experienced service technician.
  4. After completing the installation, use these instructions to check out the product

WARNING
Voltage Hazard. Can cause electrical shock or equipment damage. Disconnect power before beginning installation.

Location

Install the Comfort Control about 5 ft. (1.5m) above the floor in an area with good circulation at an average temperature. See Figure 1.

Trane-TCONT900-COMFORT-CONTROL-Thermostats-Installation-GUIDE-fig-1

Do not install the Comfort Control where it can be affected by:

  • drafts or dead spots behind doors and in
  • hot or cold air from
  • radiant heat from the sun or
  • concealed pipes and
  • unheated (uncooled) areas such as an outside wall behind the Comfort

Sub-base Installation

The Comfort Control can be mounted horizontally on the wall or on a 2-in. by 4-in. wiring box. Position the sub-base horizontally on the wall or on a 2 in. by 4 in. wiring box.

  1. Turn OFF all power to heating and cooling equipment.
  2. If an existing Comfort Control is being replaced:
    • Remove existing Comfort Control from
    • Disconnect wires from the existing control, one at a time. Be careful not to allow wires to fall back into
    • As each wire is disconnected, record the wire color and terminal
    • Discard or recycle old Comfort
  3. Separate the Comfort Control from the subbase to expose the mounting
  4. Position and level the sub-base wallplate (for appearance only). The Comfort Control functions properly even when not
  5. Use a pencil to mark the mounting
  6. Remove the sub-base from the wall and drill two 3/16 holes in the wall (if drywall) as marked. For firmer material such as plaster, drill two 7/32 in. holes. Gently tap anchors (provided) into the drilled holes until flush with the wall.
  7. Position the sub-base over the holes, pulling the wires through the wiring
  8. Insert the mounting screws in the holes and

Wiring
All wiring must comply with local electrical codes and ordinances. See Figures 2 and 3 wiring diagrams for specific equipment applications. Refer to Table 2 for terminal designations

WARNING
Voltage Hazard. Can cause electrical shock or equipment damage. Disconnect power before beginning the installation

NOTE: The maximum total cable length for the entire Comfort Control communicating system is 500 feet 18 AWG. The maximum distance of any single cable from a transformer is 250 feet 18 AWG.

  1. Loosen the terminal screws on the sub-base. Insert wires into the terminal block next to the loosened screw. See Figure

IMPORTANT
Use an 18-gauge color-coded Comfort Control cable for proper wiring. Shielded cable is not typically required. Keep this wiring at least one foot away from large inductive loads such as Electronic Air Cleaners, motors, line starters, lighting ballasts, and large distribution panels. Failure to follow these wiring practices may introduce electrical interference (noise) which can cause erratic system operation. All unused Comfort Control wires are to be grounded at indoor unit chassis ground only. The shielded cable may be required if the above wiring guidelines cannot be met. Ground the shield only to the system chassis.Trane-TCONT900-COMFORT-CONTROL-Thermostats-Installation-GUIDE-fig-2

Fig. 2. Field Wiring Diagram, Communicating Indoor Unit – Communicating Outdoor UnitTrane-TCONT900-COMFORT-CONTROL-Thermostats-Installation-GUIDE-fig-3

Fig. 3. Field Wiring Diagram, Communicating Indoor Unit – Single Stage Cooling Unit

  • Securely tighten each terminal
  • Push excess wire back in the
  • Plug the hole in the wall with nonflammable insulation to help prevent drafts from adversely affecting Comfort Control

Table 2. Terminal Designations

Terminal Designations  

Function

D Data
R Power – 24 Vac (hot)
B Power – 24 Vac (Common)

Mounting Comfort Control on Sub-base

NOTE: To remove the Comfort Control from the wall, pull it straight out.

  1. Align the terminal screw block with the pins on the back of the Comfort
  2. Push the Comfort Control straight onto the wall- plate. See Figure

Perform installation of all other system equipment

Trane-TCONT900-COMFORT-CONTROL-Thermostats-Installation-GUIDE-fig-4

Turn ON the power to the heating and cooling equipment.

INITIAL POWER-UP

Power-Up Sequence
The ComfortLinkTM II communicating Comfort Control will communicate and identify all ComfortLinkTM II components in the system.

Discovery Mode
Discovery mode begins when ComfortLinkTM II communicating Comfort Control is first installed and power is connected. For communicating equipment, the Comfort Control automatically configures the equipment type, number of stages, cycle rates for each stage, and compressor stage ratios based on the information it received during Discovery mode.

NOTE: While in Discovery mode, the LED indicator located in the upper right corner of the Comfort Control will be illuminated.

NOTE: All discovered values will be saved into memory. If a communicating device goes missing (Err 89) or changes in value (Err 126) the error will be broadcast to the comfort control screen. (Restoring communications will clear this error or see ISU 0706 to reset the system configuration).

NOTE: The communicating Comfort Control can be reset (ISU 0710) to factory default settings.

NOTE: If no equipment is connected during the Auto-Discovery process, the system mode will be stuck at “OFF” and no equipment will run.

NOTE: To change the default/discovery settings, enter the Installer Setup menu (see Table 4) and select the desired item.

NOTE: Only ISU settings with an “E” will be Auto-Discovered. Manually changing an ISU setting to an option other than “E” disables Discovery mode for that ISU setting.

NOTE: See Table 3 for default cycle rate settings.

Table 3. Typical Cycle Rate Settings

 

System

Cycles Per Hour
Steam, Gravity 1
Hydronic Heat, Condensing Gas Furnaces, Compressor Stages 3
Gas or Oil Forced Air, Auxiliary Heat 5
Electric Heat, Emergency Heat 9

Communicating Indoor Unit – Communicating Outdoor Unit

For a fully communicating system, the communicating Comfort Control will automatically configure the indoor and outdoor equipment configuration and cycle rates for each stage. See Figure 2.

Communicating Indoor Unit – Single Stage Cooling Unit
For a partially communicating system, the communicating Comfort Control will automatically configure the indoor equipment configuration and cycle rates for each stage. See Figure 3.
NOTE: The outdoor equipment configuration will default to a single-stage cooling unit.

ADJUSTING REAL-TIME CLOCK

Setting Calendar and Time
Locate and remove the tab labeled “Remove” in the lower left corner on the Comfort Control back. The tab must be removed to activate the real-time clock. See Figure 5.

Trane-TCONT900-COMFORT-CONTROL-Thermostats-Installation-GUIDE-fig-5

NOTE: If the system is not powered, the Real Time Clock battery life is approximately 20 weeks.

The Comfort Control is designed to automatically keep the current time and day in memory for up to ten years under normal use once the calendar is set. When the Comfort Control is powered, the display is ready for the calendar date to be entered. See Figure 6.Trane-TCONT900-COMFORT-CONTROL-Thermostats-Installation-GUIDE-fig-6

  1. Use the arrow keys to set the Year, Month, and Day, as shown in Figure
  2. Press the Done
  3. Use the arrow keys to set the current See Fig- ure 6.
  4. Press the Done

INSTALLER SETUP (ISU)

Trane-TCONT900-COMFORT-CONTROL-Thermostats-Installation-GUIDE-fig-7

 Comfort Control works with many different system types. The installer can use the Installer Setup menu to change factory settings to customize installations. See Table 4.

Entering Installer Setup
Follow these steps to enter the Installer Setup:

  1. Be sure the Comfort Control is
    NOTE: If necessary, press the Done key to return to the home screen.
  2. Press and release the system
  3. Press and hold the two blank keys on either side of the center key for approximately five seconds until the screen changes. See Figure
  4. Release the two blank keys when the screen on the Comfort Control matches the screen in Figure
  5. See Figure 8 to review how the Comfort Control keys are used during Installer See Table 4 for the Installer Setup Numbers and Settings.
  6. Press the Done key to exit the Installer Setup- screen.

NOTE: Manually changing an ISU setting to an option other than “E” disables Discovery mode for that ISU setting. If power is lost, all custom settings are retained in the memory.

Table 4. Installer Setup Menu

 

Selection

Installer Setup Number (ISU) Factory Setting Choices  

Comments

Option Description
Date (Year Upper) 0120 20 20, 21 Select the first two digits of current calendar year (20 for 2007) 2001-2178 available.
Date (Year Lower) 0130 06 00-99 Select the last two digits of current calendar year (07 for the year 2007) 2001-2178 available.
Date (Month) 0140 1-12 Select number that represents current calendar month
Date (Day) 0150 1-31 Select number that represents current calendar date
 

Selection

Installer Setup Number (ISU) Factory Setting Choices  

Comments

Option Description
Schedule Options 0160 4 0, 4 0 – Non-programmable

4 – 7 Day programmable

When ISU0160 is changed from 0 (non-programmable

to 4 (programmable), “Permanent Hold” will display under the time icon. This goes away when the schedule key is hit or when the schedule menu is entered.

Restore Energy Star Schedule 0165 0 0, 1 0 – No

1 – Resets the schedule to default Energy Star

No ISU or USU settings affected.
System Selection 0172 E E, 1-3 E – Auto-Discover 1 – Heat/Cool

2 – Heat Pump

3 – Heat Only (no fan)

If no equipment is connected during the Auto- Discovery process, the system mode will be stuck at “off” and no equipment will run.
Compressor Stages 0174 E E, 0-2 E – Auto-Discover 0 – None

1 – Single Stage

2 – Two Stage/Two Step

A minimum of 1H or 1C is required.
Heater Stages 0176 E E, 0-3 E – Auto-Discover 0 – None

1 – Single Stage 2 – Two Stage

3 – Three stage

A minimum of 1H or 1C is required.
Fan Operation 0180 E E, 0, 1 E – Auto-Discover

0 – Equipment controls fan operation in heat mode (fossil).

1 – Comfort Control controls fan operation in heat mode (electric).

Only seen if ISU 0172 is set to 1.
Indoor Unit Type 0181 E E, 0, 1 E – Auto-Discover

0 – Non-variable Speed 1 – Variable Speed

Compressor Low Stage Airflow 0182 E

2 Stage =

50%

2 Step =

80%

E, 25, 30,

35, 40,

45,

50, 55,

60,

65, 70,

75,

80

E – Auto-Discover, 25% – 80% in 5%

increments

Only shown for variable speed indoor units.

Options may vary based on actual system installed.

Compressor Stage 2 Airflow 0183 100% 100 Not Auto-discovered Only shown for variable speed indoor units.

Options may vary based on actual system installed.

Heat Pump Warm Air Discharge 0185 0 0, 1 0 – Disabled = 100%

1 – Enabled = 80%

Only shown for variable speed indoor units.
Continuous Fan Airflow 0186 50 25, 30,

35,

40, 45,

50,

55, 60,

65,

70, 75,

80,

85, 90,

95,

100

25% – 100% in 5%

increments

Only shown for variable speed indoor units.
 

Selection

Installer Setup Number (ISU) Factory Setting Choices  

Comments

Option Description
Backup Heat source (Aux heat) 0200 E E, 0, 1 E – Auto-Discover 0 – Electric

1 – Fossil

HP only
1st Stage Compressor Cycles Per Hour (CPH) 0220 E E, 2-6 E – Auto-Discover 2 – 6 is available;

(3 is recommended)

Default value is 3 CPH if nothing is discovered.
2nd Stage Compressor Cycles Per Hour (CPH) 0230 E E, 2-6 E – Auto-Discover 2 – 6 is available;

(3 is recommended)

Default value is 3 CPH if nothing is discovered.
1st Stage Heater Cycles Per Hour (CPH) 0240 E E, 2-6 E – Auto-Discover 2 – 6 is available;

(3 is recommended)

Default value is 3 CPH if nothing is discovered.
2nd Stage Heater Cycles Per Hour (CPH) 0250 E E, 2-6 E – Auto-Discover 2 – 6 is available;

(5 is recommended)

Default value is 5 CPH if nothing is discovered.
3rd Stage Heater Cycles Per Hour (CPH) 0260 E E, 2-6 E – Auto-Discover 2 – 6 is available;

(5 is recommended)

Default value is 5 CPH if nothing is discovered.
Continuous Backlit 0280 0 0, 1 0 – Backlit not on continuously. Comfort Control backlight comes on with a key press.

1 – Backlit is on continuously. Comfort Control backlight will come on full brightness

with a key press and display will dim 45 seconds after the last keypress.

Changeover 0300 1 0, 1 0 – Manual Changeover 1 – Auto Changeover
Deadband 0310 3 3-9 3 – 3°F (2.0°C)

4 – 4°F (2.5°C)

5 – 5°F (3.0°C)

6 – 6°F (3.5°C)

7 – 7°F (4.0°C)

8 – 8°F (4.5°C)

9 – 9°F (5.0°C)

Shown only if automatic changeover is selected. If ISU 0380 is set to Integrated Temperature and Humidity Control (ITHC), the deadband is restricted to a range of 5 to 9.
Temperature Indication Scale 0320 0 0, 1 0 – Temperature is displayed in °F

1 – Temperature is displayed in °C

Daylight Savings 0330 2 0, 1, 2, 3 0 – Daylight savings is disabled.

1 – Daylight savings is enabled (US 1987)

2 – Daylight savings is enabled (US 2007)

3 – Daylight savings is enabled (Europe)

Set to 0 for areas that do not follow daylight savings.
Outdoor Temperature Sensor 0342 E E, 0, 1 E – Auto-Discover 0 – None

1 – Installed Sensor

All communicating outdoor units are equipped with an ambient temperature sensor that will be auto- discovered
 

Selection

Installer Setup Number (ISU) Factory Setting Choices  

Comments

Option Description
Dual Fuel Heat Pump Control 0345 1 0, 1, 2 0 – Compressor lockout only If compressor is “Failing to maintain heat”, revert to aux
1 – Heat Pump Compressor heater above balance point.
lockout and failed to
maintain heat protection
2 – Heat Pump Compressor
lockout and Auxiliary Heat
lockout and Failed to
maintain heat protection in
between. To access aux
heat lockout, select option
2.
Dual Fuel Heat Pump 0346 60 0, 30, 45, 0 – Disabled System will switch to gas
Upstage to Furnace Timer 60, 75 30 – 30 minutes

45 – 45 minutes

furnace to satisfy call for heat if second stage
60 – 60 minutes

75 – 75 minutes

compressor timer expires.
Heat Pump 0350 0, 0, 5 – 60 0 – No compressor lockout System will switch to gas
Compressor Lockout 40 (dual 5 – 5°F (-15.0°C) furnace to satisfy call for
Outdoor Temperature fuel) 10 – 10°F (-12.0°C) heat if the highest
15 – 15°F (-9.5°C) compressor stage,
20 – 20°F (-6.5°C) continuous-run timer
25 – 25°F (-4.0°C) expires.
30 – 30°F (-1.0°C)
35 – 35°F (1.5°C)
40 – 40°F (4.5°C)
45 – 45°F (7.0°C)
50 – 50°F (10.0°C)
55 – 55°F (13.0°C)
60 – 60°F (15.5°C)
Auxiliary Heat 0360 0 0, 5 – 65 0 – No auxiliary heat Not available for dual fuel
Lockout Outdoor lockout unless option 2 is selected
Temperature 5 – 5°F (-15.0°C) in ISU#0345. Default will be
10 – 10°F (-12.0°C) 50 in this case.
15 – 15°F (-9.5°C)
20 – 20°F (-6.5°C)
25 – 25°F (-4.0°C)
30 – 30°F (-1.0°C)
35 – 35°F (1.5°C)
40 – 40°F (4.5°C)
45 – 45°F (7.0°C)
50 – 50°F (10.0°C)
55 – 55°F (13.0°C)
60 – 60°F (15.5°C)
65 – 65°F (18.5°C)
1st Stage Heater Defrost Balance Point 0361 0 0, 5 – 55 0 – Disabled

5 – 5°F (-15.0°C)

10 – 10°F (-12.0°C)

15 – 15°F (-9.5°C)

Only shown if outdoor temperature is available.
20 – 20°F (-6.5°C)
25 – 25°F (-4.0°C)
30 – 30°F (-1.0°C)
35 – 35°F (1.5°C)
40 – 40°F (4.5°C)
45 – 45°F (7.0°C)
50 – 50°F (10.0°C)
55 – 55°F (13.0°C)
 

Selection

Installer Setup Number (ISU) Factory Setting Choices  

Comments

Option Description
2nd Stage Heater Defrost Balance Point 0362 40 0, 5 – 55 0 – Disabled

5 – 5°F (-15.0°C)

10 – 10°F (-12.0°C)

15 – 15°F (-9.5°C)

20 – 20°F (-6.5°C)

25 – 25°F (-4.0°C)

30 – 30°F (-1.0°C)

35 – 35°F (1.5°C)

40 – 40°F (4.5°C)

45 – 45°F (7.0°C)

50 – 50°F (10.0°C)

55 – 55°F (13.0°C)

Only shown if outdoor temperature is available.
3rd Stage Heater Defrost Balance Point 0363 25 0, 5 – 55 0 – Disabled

5 – 5°F (-15.0°C)

10 – 10°F (-12.0°C)

15 – 15°F (-9.5°C)

20 – 20°F (-6.5°C)

25 – 25°F (-4.0°C)

30 – 30°F (-1.0°C)

35 – 35°F (1.5°C)

40 – 40°F (4.5°C)

45 – 45°F (7.0°C)

50 – 50°F (10.0°C)

55 – 55°F (13.0°C)

Only shown if outdoor temperature is available.
Defrost Heater Selection 0364 0 – 7 0 – None

1 – Aux1

2 – Aux2

3 – Aux3

4 – Aux1 and Aux2 5 – Aux2 and Aux3 6 – Aux1 and Aux3

7 – Aux1 and Aux2 and Aux3

Default will be preset to the maximum number of aux heat stages available.

Only shown if Heater Defrost Balance Point(s) are disabled by selecting “0” in ISU 0361, 0362 and/

or 0363.

Discharge Temperature Sensor 0365 E E, 0, 1 E – Auto-Discover 0 – None

1 – Remote Sensor Installed

For future use. Leave at factory default setting “E”
Indoor Humidity Sensor 0370 1 0, 1, 2 0 – Disabled

1 – Internal sensor 2 – Remote sensor

Indoor Humidification Control 0372 E, 0 E, 0, 1, 2 E – Auto-Discover 0 – Off

1 – Relative Humidity Setpoint

2 – Dewpoint Control

Auto-Discover will discover “0”

Dewpoint Control with Frost Protection requires outdoor temperature sensor

Humidifier Fan Action 0374 2 1, 2 1 – Fan turns on with Humidifier

2 – Humidify only when Heat is on

Only visible when ISU 0372 enabled. Fan will run for 2 minutes after humidifier turns off.
Indoor Dehumidification Control 0380 1 0, 1, 4 0 – Off

1 – Integrated Temperature and Humidity Control – ITHC (RH Setpoint)

4 – Trane Droop (RH Setpoint)

Deadband limited when in Auto- Changeover Mode and ITHC is enabled.

See “Dehumidification” on page 19.

Comfort-RTM Delay 0381 0 0, 1, 2 0 – No Delay

1 Comfort-RTM 15 sec

2 – Comfort-RTM 30 sec

Only shown for non-variable speed indoor units
Dehumidification Maximum Droop 0383 1 1, 2, 3 1 – 1°F (0.5°C)

2 – 2.0°F (1.0°C)

3 – 3°F (1.5°C)

Only shown if ITHC is selected
 

Selection

Installer Setup Number (ISU) Factory Setting Choices  

Comments

Option Description
Dehumidification Airflow 0387 100 80 – 100 80 – 80% Airflow

85 – 85% Airflow

90 – 90% Airflow

95 – 95% Airflow

100 – 100% Airflow

Only shown for variable speed indoor units. See Advanced Features section for more information
Trane Proprietary Humidity Control 0388 1 0, 1 0 – Disabled

1 – Enabled

Not shown if ISU0380 is set to 0.

See Advanced Features section for more information

Furnace Filter 1 Change Reminder 0500 E, 0 E, 0 – 14 E – Auto-Discover

0 – Disabled (reminder off) 1 – 10 run time days

2 – 30 run time days

3 – 60 run time days

4 – 90 run time days

5 – 120 run time days

6 – 180 run time days

7 – 270 run time days

8 – 365 run time days

9 – 30 continuous days

10 – 60 continuous days

11 – 90 continuous days

12 – 120 continuous days

13 – 180 continuous days

14 – 365 continuous days

When set to Auto-Discover (and the discovered value is not 0=disabled), the Comfort Control will display the filter timer value it receives from the ComfortLinkTM II communicating filtering device on the More screen. To reset the filter timer of the ComfortLinkTM II communicating filtering device, simply press the More key to access the filter timer value and then press the Reset key. If no ComfortLinkTM II communicating filtering device has been discovered, the auto- discovered value will default to 0.
When not set to Auto- Discover (and not set to 0=disabled), the Comfort Control will display its internal filter timer on the More screen.

To reset the Comfort Control’s internal timer, simply press the More key to access the filter timer value and then press the Reset key.

 

Selection

Installer Setup Number (ISU) Factory Setting Choices  

Comments

Option Description
Furnace Filter 2 Change Reminder 0501 E, 0 E, 0 – 14 E – Auto-Discover

0 – Disabled (reminder off) 1 – 10 run time days

2 – 30 run time days

3 – 60 run time days

4 – 90 run time days

5 – 120 run time days

6 – 180 run time days

7 – 270 run time days

8 – 365 run time days

9 – 30 continuous days

10 – 60 continuous days

11 – 90 continuous days

12 – 120 continuous days

13 – 180 continuous days

14 – 365 continuous days

When set to Auto-Discover (and the discovered value is not 0=disabled), the Comfort Control will display the filter timer value it receives from the ComfortLinkTM II communicating filtering device on the More screen. To reset the filter timer of the ComfortLinkTM II communicating filtering device, simply press the More key to access the filter timer value and then press the Reset key. If no ComfortLinkTM II communicating filtering device has been discovered, the auto- discovered value will default to 0.
When not set to Auto- Discover (and not set to 0=disabled), the Comfort Control will display its internal filter timer on the More screen.

To reset the Comfort Control’s internal timer, simply press the More key to access the filter timer value and then press the Reset key.

Humidifier Pad 0510 E, 0 E, 0 – 3 E – Auto-Discover When controlling humidifier
Replacement 0 – Disabled settings, use run time days.
Reminder 1 – 90 continuous days Otherwise, use calendar
(30 run time days) days.
2 – 180 continuous days
(60 run time days)
3 – 365 continuous days
(90 run time days)
Adaptive Intelligent Recovery 0530 1 0, 1 0 – Conventional recovery is activated

1 – Adaptive Intelligent Recovery control is activated

Adaptive Recovery starts recovery early to reach setpoint by start of program period.
Number of Periods 0540 4 2, 4 2 – Two Periods available (Wake, Sleep)

4 – Four Periods available (Wake, Leave, Return, Sleep)

Selection applies to all days of the week.

Not shown if nonprogrammable is selected.

Heat Temperature Range Stop 0600 90 50 – 90 Highest heating setpoint. Temperature range (1°F increments) of heating setpoint. Shown in 1/2°C
Cool Temperature Range Stop 0610 60 60 – 99 Lowest cooling setpoint. Temperature range (1°F Shown in 1/2°C
increments) of cooling
setpoint.
Minimum Noncompressor On Time 0620 3 0 – 15 Minimum number of minutes non-compressor (heat) equipment is on.
 

Selection

Installer Setup Number (ISU) Factory Setting Choices  

Comments

Option Description
Minimum Compressor On Time 0630 3 0 – 15 Minimum number of minutes compressor is on.
Clock Format 0640 12 12, 24 12 – 12-hour clock format 24 – 24-hour clock format
Extended Fan On Time Heat 0650 0 0, 30, 60,

90 or 120

Fan operation is extended 0, 30, 60, 90 or 120

seconds after call for heat ends.

Only shown for nonvariable speed indoor units.
Compressor Heat Blower Off Delay Profile 0651 5 0 – 5 0 – Disabled

1 – 0.5 min @ 35%

2 – 0.5 min @ 50%

3 – 1.5 min @ 50%

4 – 0.75 min @ 100%

5 – 1.5 min @ 100%

Only shown for variable speed indoor units.
Extended Fan on time control 0660 90 0, 30, 60,

90 or 120

Fan operation is extended 0, 30, 60, 90 or 120

seconds after call for cool ends.

Only shown for nonvariable speed indoor units.
Compressor Cool Blower Off Delay Profile 0661 5 0 – 5 0 – Disabled

1 – 0.5 min @ 35%

2 – 0.5 min @ 50%

3 – 1.5 min @ 50%

4 – 0.75 min @ 100%

5 – 1.5 min @ 100%

Only shown for variable speed indoor units.
Compressor Heat Fan On Delay Profile 0665 0 0, 1, 5,

10, 20,

30

0 – Disabled

1 – Enabled – 50% for 1 minute (V.S. only)

5 – 5 seconds

10 – 10 seconds

20 – 20 seconds

30 – 30 seconds

For Variable Speed indoor units: choices are 0 and 1. For Non-variable Speed indoor units: choices are 0, 5, 10, 20, and 30.
Compressor Cool Fan On Delay Profile 0667 0 0, 1, 5,

10, 20,

30

0 – Disabled

1 – Enabled – 50% for 1 minute (V.S. only)

5 – 5 seconds

10 – 10 seconds

20 – 20 seconds

30 – 30 seconds

For Variable Speed indoor units: choices are 0 and 1. For Non-variable Speed indoor units: choices are 0, 5, 10, 20, and 30.
Keypad Lockout 0670 0 0, 1, 2 0 – Unlocked keypad

1 – Partially locked keypad 2 – Fully locked keypad

Unlocked – all functions are available.

Partially locked – only temperature up and down keys and ability to enter and modify installer setup mode are available.

Fully locked – only ability to enter and modify installer setup mode are available.

Temperature Control in Heat 0680 2 1, 2, 3 1 – Less aggressive temperature control (could cause temperature undershoot)

2 – Standard temperature control in heating

3 – More aggressive temperature control (could cause temperature overshoot)

Applies to recovery ramp and use of auxiliary heat during recovery.
 

Selection

Installer Setup Number (ISU) Factory Setting Choices  

Comments

Option Description
Temperature Control in Cool 0690 2 1, 2, 3 1 – Less aggressive temperature Applies to recovery ramp and use of cooling stages
control (could cause during recovery.
temperature
undershoot)
2 – Standard temperature
control
in cooling
3 – More aggressive
temperature
control (could cause
temperature
overshoot)
Temperature Display Offset 0700 0 -3, -2, -1,

0, 1, 2, 3

-3°F (-1.5°C)

-2°F (-1.0°C)

-1°F (-0.5°C)
0°F (0.0°C)
1°F (0.5°C)
2°F (1.0°C)
3°F (1.5°C)
Humidity Display Offset 0701 0 -5, -4, -3,

– 2, -1, 0,

-5%

-4%

1, 2, 3, 4, -3%
5 -2%
-1%
0%
1%
2%
3%
4%
5%
Reset Discovered Device 0706 0 0, 1 0 – No

1- Yes

Will clear the equipment change alert (Err 126 – see
Alert Code Addendum, form
18-HD32D2-1/69-2009) by
re-initializing Auto
Discovery
Restore Factory Defaults 0710 0 0, 1 0 – No Comfort Control reset Only the calendar setting and time are retained.
1 – Resets all Installer
Setup options to default
values and resets schedule
to default setting
(Energy Star).

OPERATION

Using the Comfort Control
System and Fan Settings
The System’s default setting is Heat unless no Heat stage is discovered/configured. The fan’s default setting is Auto.

SYSTEM SETTINGS
Heat: Controls heating system.
Off: Heating and cooling are off.
Cool: Controls cooling system.
Auto: Automatically changes between heating and cooling systems, depending on indoor temperature. (See Installer Setup section.)
Em Heat: The compressor is locked out and auxiliary heat cycles to maintain temperature (Used only for heat pump systems with backup heat.) The maximum allowable emergency heat stages is 3.

FAN SETTINGS
Pressing the fan key selects whether the indoor fan motor runs in the On, Automatic, or Circulation mode. The fan setting can be programmed into the Comfort Control schedule for each period (Wake, Leave, Return, Sleep). On: Fan runs continuously Auto: The fan is automatically following the fan schedule. (See the Fan Schedule section for more information.) Circ: Circulation control will provide a variable circulation determined by the Adaptive Intelligent Circulation (AIC) an algorithm running the fan between 20% and 60% of the time.

LED Indication

An LED indicator is located in the upper right corner of the Comfort Control. It is only visible when lighted:

  • It indicates that there is an Alert.
  •  It indicates that the Comfort Control is in Discovery mode.

LED Indication
FILTER INDICATION
The Comfort Control can track up to two filter timers by a total fan run time or calendar days. This feature can be used to tell the homeowner when to replace the Furnace filter or clean the Air Cleaner cells: Select filter timer reset time: Total Fan Run Time: the number of run time days for the filter timer to count down from 0, 10, 30, 60, 90, 120, 180, 270, or 365 days. (One run time day represents 24 hours of continuous fan/system run time.) Calendar Days: the number of days for the filter timer to count down from 0, 30, 60, 90, 120, 180, or 365 days. To activate this feature, select a value other than 0 (disabled). See the Owner’s Guide for more detailed information.

Pre-programmed
Table 5 shows the Energy Star default program settings. See the Owner’s Guide for complete instructions on changing the program.

Table 5. Energy Star Default Program Settings

 

Period

 

Time

Heat Setpoint Cool Setpoint Fan Setting
Wake 6:00 AM 70°F (21°C) 78°F (25.5°C) Auto
Leave 8:00 AM 62°F (16.5°C) 85°F (29.5°C) Auto
Return 6:00 PM 70°F (21°C) 78°F (25.5°C) Auto
Sleep 10:00 PM 62°F (16.5°C) 82°F (28°C) Auto

Alert Code Numbers
The Comfort Control can receive Alert codes from any communicating equipment via the ComfortLinkTM II bus. The Comfort Control will illuminate the Red “Service” LED and toggle between the main screen and a screen showing the Alert code number. When multiple Alert codes exist simultaneously, the display will cycle through each code (showing a maximum of the 5 most recent Alerts) and return to the main screen. See the Alert Code Addendum (form 18-HD32D2-1/69-2009) for a listing of all equipment Alert codes.

Equipment Damage Hazard. Minimum compressor off-time is bypassed during Installer System Test.
Avoid cycling compressors quickly. Observe compressor protection period.

System Checkout

 Installer System Test
The Installer System Test mode is used to test the Comfort Control operation with HVAC equipment. See Table 7. System configuration determines which tests are available and the number of stages shown. While in System Test mode, the minimum off time is bypassed. the Installer Test is part of the Installer Setup options. Enter the Installer Setup screen and press the Down arrow key for quick access to the test selection(s).

NOTE: Changing tests will turn equipment off.
NOTE: Entering Installer Setup will turn the equipment off. NOTE: NOTE: Charge AssistTM mode is not available during Installer System Tests.
NOTE: Test modes time out after 5 minutes.

Table 6. Installer System Tests

 

Selection

Installer Setup Number Factory Setting Choices Comments
Option Description
Installer Test Cool Test 1 0 0, 1, 2, 3 0 – Cool is off

1 – Cool stage 1

2 – Cool stage 1, 2

3 – Cool stage 1, 2, 3

Not shown if ISU 0172 is set to 3 or if ISU0174 is set to 0.

If Discharge Air Temperature Sensor is available, Press the More key to show the Discharge Air Temperature value.

Installer Test Fan Test 2 0 0, 1 0 – Fan is off 1 – Fan on Not shown if ISU 0172 is set to 3.

If Discharge Air Temperature Sensor is available, Press the More key to show the Discharge Air Temperature value.

 

Selection

Installer Setup Number Factory Setting Choices Comments
Option Description
Installer Test Heat Test 3 0 0, 1, 2, 3,

4

0 – Heat is off

1 – Heat stage 1

2 – Heat stage 1, 2

3 – Heat stage 1, 2, 3

4 – Heat stage 1, 2, 3, 4

Not shown if ISU 0176 is set to 0.

If Discharge Air Temperature Sensor is available, Press the More key to show the Discharge Air Temperature Air Value.

Installer Test Emergency Heat Test 4 0 0, 1, 2, 3 0 – EmHeat is off

1 – EmHeat stage 1

2 – EmHeat stage 1, 2

3 – EmHeat stage 1, 2, 3

If Discharge Air Temperature Sensor is available, Press the More key to show the Discharge Air Temperature value.

Available only if heat pump with auxiliary heat is selected.

Installer Test Humidifier Test 5 0 0, 1 0 – Humidifier off 1 – Humidifier on Not shown if ISU 0372 is set to 0.

Fan will follow Hum setting.

Installer Test Dehumidification Function Test 6 0 0, 1 0 – Dehumidifier off 1 – Dehumidifier on Not shown if ISU 0380 is set to 0.

Fan will follow DeHum setting.

ADVANCED FEATURES

Adjustable Continuous Air Flow
The Continuous Fan air flow is user adjustable from 25% to 100% in 5% increments either by entering the User Setup menu or the Installer Setup menu (see Table 4, ISU Number 0186).
NOTE: CONTINUOUS fan mode during COOLING operation may not be appropriate in humid climates. If the indoor air exceeds 60% relative humidity or simply feels uncomfortably humid, it is recommended that the fan only be used in the AUTO mode.

Control Response Rate
A set of more/ less aggressive Proportional-Integral control constants can be chosen to increase/decrease the responsiveness of the temperature control performance. Choosing a more aggressive rate may cause overshooting. Furthermore, selecting a less aggressive rate may result in undershooting.

Cycle Rate
Cycle rate is the selected number of system cycles per hour at 50% load. If the cycle rate were set to 3, each ON/ OFF cycle would be 20 minutes long when operating at 50% load. The total ON and/or OFF times depend on the actual indoor space load. A shorter cycle rate may be desired for the Heating mode to maintain tighter control to the indoor setpoint. A longer cycle rate may be desired for the Cooling mode to allow the system to remove moisture from the air and improve indoor comfort.

Auto Changeover
When the system mode is set to Auto, the control automatically switches between heating and cooling modes to maintain the desired comfort level.

Setpoint Deadband
The number of degrees separating Heating and Cooling setpoints is user adjustable from 2 to 9 degrees. When the control is set to Auto, and the cooling setpoint is changed to a cooler setpoint, the heating setpoint will also change to maintain the selected deadband. The same action occurs when the Heating setpoint is changed to a warmer temperature.
NOTE: The deadband is restricted to a range of 5 to 9 if ISU 0380 is set to Integrated Temperature and Humidity Control (ITHC).

Backlit Display
When the continuous backlight is disabled, the liquid crystal display will illuminate only when a touchscreen key is pressed to improve visibility. The backlight stays on for 45 seconds after the last touchscreen key press. When a continuous backlight is enabled, the liquid crystal display will remain illuminated continuously. The display will dim to half brightness 45 seconds after the last touch screen key press.

Filter Reminders
The Comfort Control can track up to two filter timers by a total fan run time or calendar days. When the preset timer(s) has expired to remind the homeowner that it is time to change the filter(s), “Change” and then “Filter” will automatically flash. To reset either filter timer, simply press the More key to access the filter timer value and then press the Reset key. Once the timer has been reset the filter timer value can be viewed at any time by simply pressing the More key until the filter timer is displayed on the screen.
NOTE: Both the filter timers are auto-discoverable ISU settings. If no ComfortLinkTM II communicating filtering device has been discovered, the auto-discovered value will default to 0. To enable one or both timers, change ISU 0500 and/or ISU 0501 to a value other than 0.

Fan Selections
Pressing the Fan key selects whether the indoor fan motor runs in the On, Automatic, or Circulation mode. In On mode, the fan motor runs continuously. The fan automatically follows the fan schedule in Automatic mode. Circulation control will provide a variable circulation determined by the Adaptive Intelligent Circulation (AIC) algorithm running the fan between 20% and 60% of the time. Each schedule period (Wake, Leave, Return, Sleep) can be programmed with a specific fan setting (On, Automatic, or Circulation).

Screen Locked
Locking the control’s touchscreen keys can help prevent unwanted tampering with or changing of control settings. The Comfort Control can either be fully locked or partially locked. Both options continuously display “Screen Locked” on the screen. Changing ISU Number 0670 to 0 will unlock the keys and “Screen Locked” will disappear.

Installer System Tests
The built-in Installer System Test mode allows the servicer to quickly and easily test the Comfort Control’s operation with HVAC equipment and makes diagnostic procedures a snap. System configuration determines which tests are available and the corresponding number of stages shown (see Table 7, Tests 1 – 6 for details).

Default Factory Settings
The Comfort Control is shipped with a set of factory default settings. The factory default settings can be restored at any time using the Installer Setup menu (see Table 4, ISU Number 0710).
NOTE: Before you perform Auto-Discovery Mode (ISU Number 0710), is it recommended that you record all your user settings. All user setting choices will be reset to factory defaults in Auto-Discovery Mode.

Wait for Indicator
“Wait” will be displayed when the setpoint is changed in the direction of calling for additional system capacity or the outdoor unit is in Charge AssistTM mode. “Wait” indicates system time delays are being enforced, and the control is adjusting to the new setting.

Trane-TCONT900-COMFORT-CONTROL-Thermostats-Installation-GUIDE-fig-8

Calibrate Indoor Temperature
This option allows the calibration of the room temperature sensor. The selected number is a number of degrees, plus or minus, which will be added to the actual temperature. The number can range between +3 and -3 degrees in 1-degree increments. The factory default is 0. The adjusted value will be used as the temperature for both the display and control action.

Calibrate Indoor Humidity
This option allows the calibration of the indoor humidity sensor. The selected number is the percent relative humidity, plus or minus, which will be added to the actual indoor humidity. The number can range between +5% and -5% in 1% increments. The factory default is 0. The adjusted value will be used as the humidity for both display and control action.

Outdoor Temperature Sensor
For accuracy, the initial reading of the outdoor temperature sensor requires five minutes to stabilize. See the Sensor Instructions for installation information.
NOTE: If the device is using an outdoor sensor for control and the outdoor temperature sensor becomes unavailable, the display will show dashes “- -” and generate an Alert. If the device is not using an outdoor sensor for control and the outdoor temperature sensor becomes unavailable, no outdoor value will be displayed. The Comfort Control will not send an Alert.

Humidification

Indoor Humidification Control
This feature attempts to control the indoor humidity to the user’s humidification setpoint using a humidifier. The humidification setpoint can range between 10% and 60% in 5% increments. When enabled, the default humidification setpoint is 50%.

Frost Control
The Frost Control requires an outdoor sensor and a humidifier. The Comfort Control calculates the possibility of condensation or frost forming by using the outside temperature and inside temperature to determine the dewpoint. When the dewpoint could cause frost or condensation, the humidification request will not be honored.The Frost Setting can be accessed by pressing the More key until the Frost Setting is displayed on the screen. It has a value range of 0 to 10, with 0 representing glass with poor insulation and 10 representing glass with perfect insulation. If the factory setting (5), results in too much condensation or frost on the windows, lower the setting. When the air seems too dry, raise the setting.

Dehumidification
Integrated Temperature and Humidity Control (ITHC) The dehumidification control attempts to control the indoor humidity to the user’s dehumidification setpoint by running the compressor. The dehumidification setpoint can be accessed by pressing the More key until the dehumidification setpoint is displayed on the screen. The setpoint can range between 40% and 80% in 5% increments. When enabled, the default dehumidification setpoint is 50%. In extremely high humidity conditions, the Comfort Control keeps the compressor running for up to 3°F (-1.7°C) below the temperature setpoint. It does this while trying to achieve the desired dehumidification setpoint and balancing that with the temperature setpoint. The maximum allowable dehumidification droop can be selected in ISU 0383.

Trane Droop
Trane Droop is a feature that cycles the compressor on to improve indoor comfort by removing moisture from the air. The Droop cycle is activated when the indoor humidity is above the user’s dehumidification setpoint. When this function is active, the Comfort Control will control the temperature at 1 or 2 degrees F below the cooling setpoint. The Droop cycle is deactivated when the indoor humidity drops below the user’s dehumidification setpoint. If the indoor humidity sensor fails, the droop logic will always be enabled while in cooling mode.

Comfort-RTM Delay
When the indoor humidity is above the user’s dehumidification setpoint, Comfort-RTM Delay will remove humidity from the air by implementing a blower turn-on delay of 15 or 30 seconds to “pre-chill” the coil. Comfort- RTM Delay applies to non-variable speed indoor unit types only.

Dehumidification Airflow
During any dehumidification control option, a lower-speed fan can be activated. The settings range from 80% to 100% in 5% increments (see Table 4, Installer Setup number 0387). The default dehumidification airflow is 100%.

Trane Proprietary Humidity Control
When enabled, this feature will disable any blower-off delays and disable continuous fan mode when the indoor humidity is above the dehumidification setpoint. This will help prevent coil condensation from being evaporated back into the air stream.

NOTE: This feature, ISU 0388, is not shown unless some form of dehumidification control is selected.

Special Heat Pump Features
Auxiliary Heat Lockout Temperature When an outdoor temperature sensor has been discovered/ enabled, none of the installed auxiliary heat stages will turn on during heating operation above the selected outdoor temperature. When the outdoor temperature is less than the auxiliary heat lockout temperature (ISU Number 0360), the Comfort Control may cycle the indoor heat on and off to satisfy the load. During defrost, this outdoor temperature setting is ignored and the defrost heater balance point outdoor temperature thresholds are used.
NOTE: For Dual Fuel applications, if the heat pump fails to maintain the heat while the outdoor temperature is above the auxiliary lockout temperature, the furnace will be used until the setpoint is reached, at which time heat pump operation will resume.

Compressor Heat Lockout Temperature
When an outdoor temperature sensor has been discovered/ enabled, only the installed auxiliary heat stages will turn on during heating operation below the selected outdoor temperature. When the outdoor temperature is greater than the compressor heat lockout temperature (ISU Number 0350), the heat pump attempts to satisfy the load. If the heat pump can not satisfy the load and the outdoor temperature is less than the compressor lockout temperature (ISU Number 0350), the Comfort Control will transition to auxiliary heat operation and will turn off the heat pump. During defrost, this outdoor temperature setting is ignored and the defrost heater balance point outdoor temperature thresholds are used.
NOTE: There is a 5°F deadband between the Compressor and auxiliary heat lockout temperatures.

Operation in Heat Mode
When the outdoor temperature is below the compressor lockout temperature, only the auxiliary heat operates. When the outdoor temperature is above the auxiliary lockout temperature, only the Compressor operates. See Figure 9. When the outdoor temperature is between the two temperatures, both the Compressor and auxiliary heat operate.

Trane-TCONT900-COMFORT-CONTROL-Thermostats-Installation-GUIDE-fig-9

Defrost Heater Balance Point Control
When an outdoor temperature sensor has been discovered/ enabled, a separate outdoor temperature turn-on threshold can be set for each installed heater stage during defrost in Installer Setup Numbers 0361 -0363. If the balance point for a particular heater stage is disabled, that heater stage will be used during every defrost cycle independent of the outdoor temperature.
NOTE:  If the outdoor sensor is no longer report- ing, all available heater stages will be used during defrost. When an outdoor temperature sensor has not been discovered/enabled, the stage or combination of stages to be used during defrosting can be set in Installer Setup Number 0364.

Operation in Emergency Heat Mode
When the Comfort Control is placed in Emergency Heat mode, the compressor and auxiliary lockout features are turned off. In the Emergency Heat mode, the compressor is locked out and only the auxiliary heat operates. The Comfort Control is capable of controlling up to a maximum of three Emergency Heat stages.

Heat Pump with Fossil Fuel Heat (Dual Fuel) and Outdoor Temperature Sensor
In this operation, there is no external fossil fuel kit (dual fuel kit) installed; the Comfort Control controls this function. During the transition between Furnace and heat pump operation, there is a minimum Comfort Control time delay of 45 seconds between the Furnace turning off and the heat pump turning on and 0 seconds between the heat pump turning off and the Furnace turning on.
NOTE: If the outdoor is missing or no longer reporting, the control algorithm will revert back to a fossil fuel-only application.For non-communicating equipment, configure the Comfort Control by:

  1. Choose Heat Pump Application in Installer Setup Number 0172.
  2. Choose Fossil Fuel Option as the backup heat source in Installer Setup Number 0200.
  3. Outdoor Temperature Sensor for Control Option is automatically chosen in Installer Setup Number 0342.
  4. Choose the appropriate Dual Fuel Heat Pump Control in Installer Setup Number 0345.
  5. Choose the appropriate Compressor Lockout Tem-perature in Installer Setup Number 0350.
  6. If the heat pump auxiliary lockout was selected in Installer Setup Number 0345, choose the appropriate Heat Pump Auxiliary Lockout Temperature in Installer Setup Number 0360.
  7. Choose appropriate Defrost Balance Point Temperatures in Installer Setup Numbers 0361 – 0363.

Heat Pump with Electric Auxiliary (Backup) Heat and Outdoor Temperature Sensor
For non-communicating equipment, configure the Comfort Control by:

  1. Choose Heat Pump Application in Installer Setup
  2. Choose Electric Option as the Auxiliary (Backup) Heat Source in Installer Setup Number 0200.
  3. Choose the appropriate Outdoor Temperature Sensor for Control Option in Installer Setup Number 0342. If Outdoor Temperature Sensor was discovered/enabled in Installer Setup
  4. Number 0342, choose the appropriate Compressor Lockout Temperature in Installer Setup Number 0350.
  5. If Outdoor Temperature Sensor was discovered/enabled in Installer Setup Number 0342, choose the appropriate Heat Pump Auxiliary Lockout Temperature in Installer Setup Number 0360.
  6. If Outdoor Temperature Sensor was discovered/ enabled in Installer Setup Number 0342, choose appropriate Defrost Balance Point Temperatures in Installer Setup Numbers 0361 – 0363.

TROUBLESHOOTING GUIDE

Refer to Table 8 for troubleshooting information.

Symptom Possible Cause Action
Red service LED is illuminated and the display alternates between Home screen and Alert Code screen. Alert Code present Refer to the Alert Code Addendum (form 18-HD32D2-1/69-2009).
Display will not come on. 1. Blown fuse or tripped circuit breaker.

2. Indoor unit power switch OFF.

3. Indoor unit blower compartment door or panel loose or not properly installed.

4. Wire broken/shorted; or R and D or B and D are reversed.

1. Replace fuse or reset breaker.

2. Turn power switch to ON.

3. Replace door panel in proper position to engage safety interlock or door switch on furnace.

4. Check R, B, D wiring.

Indoor temperature display is incorrect. Temperature display needs calibration. Calibrate Sensor – ISU 0700
Indoor humidity display is incorrect. Indoor humidity display needs calibration. Calibrate Sensor – ISU 0701
Symptom Possible Cause Action
Outdoor temperature display shows “–” or the outdoor temperature is not displayed. 1. Outdoor temperature sensor open, shorted, not reporting, or not installed.

2. Outdoor sensor field wiring open or shorted.

1. Replace/Install outdoor sensor.

2. Check/repair outdoor sensor field wiring.

Indoor temperature display shows “–”. Indoor temperature sensor open or shorted. Replace control.
Temperature setting will not change (e.g. Cannot increase heating setpoint or reduce cooling setpoint). 1. Upper and/or lower temperature limits were reached.

2. Keys are fully locked. “Screen Locked” is displayed on LCD.

1. Check the temperature setpoints: Heating limits (ISU 0600) are 40°F – 90°F (4.4°C – 32.2°C).

Cooling limits (ISU 0610) are 60°F – 99°F (15.5°C – 32.2°C).

2. Unlock keypad – ISU 0670.

Room temperature overshoots when the Heat/ Cool setting is changed more than 2 degrees. 1. Oversized heating/cooling equipment under current conditions. Control cannot respond fast enough to prevent overshooting.

2. Improper location of comfort control.

1. Set Control Response rate to “Aggressive” – ISU 0680, 0690

2. Select a location that prevents the Comfort Control from being directly exposed to air currents from supply registers.

Heating will not come on. 1. System Mode not set to Heat.

2. Minimum off time delay being enforced.

3. Loose connection to control or system.

4. Heating system may need service.

1. Set Mode to heat and raise the setpoint above room temperature.

2. If heating does not come on within 5 minutes, checking heating equipment.

3. Check/repair connections.

4. Repair system.

Cooing will not come on. 1. System Mode not set to Cool.

2. Minimum off time delay being enforced.

3. Loose connection to control or system.

4. Cooling system may need service.

1. Set Mode to cool and lower the setpoint above room temperature.

2. If cooling does not come on within 15 minutes, checking cooling equipment.

3. Check/repair connections.

4. Repair system.

Heat ON or Cool ON is displayed, but no warm air or cool air is coming from the registers. 1. The heating equipment turns on the fan when the furnace has warmed up.

2. Heating or cooling equipment is not operating.

1. Wait one minute after Heat ON is displayed and then check the registers.

2. Check Heating and/or Cooling equipment.

Control does not respond to keypad screen presses. 1. Keys are fully locked. “Screen Locked” is displayed on LCD.

2. Keypad failure.

1. Unlock keypad – ISU 0670.

2. Replace control.

Fan does not operate properly in heat or cool mode. 1. Heating or cooling equipment inoperative. 1. Repair system.
Fan runs all of the time. 1. Fan mode is set to ON – continuous.

2. Fan scheduled to run continuously.

3. Indoor equipment may need service.

1. Set fan mode to AUTO or CIRC.

2. Reprogram fan schedule, if desired.

3. Check Indoor equipment.

Fan is set to “On” but not running. 1. Trane Proprietary Humidity Control. Verify that the Dehumidification setpoint is below the actual indoor humidity. See “Trane Proprietary Humidity Control” on page 19 for additional information.
Cooling cycles too fast or too slow (narrow or wide temperature swing). The location of the control and/or the size of the cooling system may be influencing the cycle rate. Verify/adjust cycle rates – ISU 0220, 0230.
Symptom Possible Cause Action
Heating cycle too fast or too slow (narrow or wide temperature swing). The location of the control and/or the size of the heating system may be influencing the cycle rate. Verify/adjust cycle rates – ISU 0240, 0250, 0260.
Only Furnace heat; no heat pump heating in Dual Fuel mode. 1. Outdoor temperature sensor is missing or no longer reporting.

2. Outdoor temperature is below the Compressor Lockout Temperature setting.

1. Check/ repair outdoor sensor field wiring.

2. Lower the Compressor Lockout Temperature setting, if desired.

Cannot change system mode to Heat or Cool mode. 1. Comfort Control not configured properly. 1. Check/verify System Selection – ISU 0172.
No equipment is running and can not change the mode from “OFF”. Equipment was not connected during Auto-Discovery mode. 1. Check/verify wiring connection and cycle power to components.

2. Cycle Power – System will Re-initiate Auto-Discover.

U.S. Registered Trademark  Copyright © 2008 Trane All Rights Reserved
Pub. No. 18-HD32D1-2
69-2079—05 M.S. Rev. 11-08

REFERENCE:

Download Manual:

Trane TCONT900 COMFORT CONTROL INSTALLERS GUIDE

TRANE-LOGO

Trane TCONT900 COMFORT CONTROL INSTALLERS GUIDE

The post Trane TCONT900 COMFORT CONTROL Thermostats Installation GUIDE appeared first on thermostat.guide.



source https://thermostat.guide/trane/trane-tcont900-comfort-control-thermostats-installation-guide/

No comments:

Post a Comment

Blyss Valkla Digital Thermostat User Manual

Blyss Valkla Digital Thermostat What is in the box Check the contents of the packaging and the visual condition of the products. Contents of...