SALUS T105 Programmable Thermostat
Introduction
T105 / T105RF is a programmable, weekly regulator that is used to control room temperature in heating or cooling systems. Before first use please read this manual carefully. Use only AA 1,5V alkaline batteries in the thermostat. Place batteries into battery slot located under the cover. Do not use rechargeable batteries.
Product Compliance
This product complies with the following EC Directives: Electromagnetic Compatibility 2004/108/CE, Low Voltage Directive 2006/95/EEC, Directive 93/68/EEC and 99/5/EC. Full information is available on the website www.saluslegal.com.
Safety Information
Use in accordance with national and EU regulations. Use the device as intended, keeping it in dry condition. Product for indoor use only. Installation must be carried out by a qualified person in accordance to national and EU regulations.
Technical specification
Wired thermostat T105
Power supply | 2 x AA batteries |
Rating max | 5 (3) A |
Outputs | Voltage-free NO/COM relay |
Temperature range | 7 – 30°C |
Wireless thermostat T105RF
Thermostat supply | 2 x AA batteries |
Receiver supply | 230 V AC 50 Hz |
Receiver rating max | 16 (5) A |
Receiver outputs | Voltage-free NO/COM relay |
Temperature range | 7 – 30°C |
Proper thermostat placement
LCD Icon description and button functions
- Day of the week indicator
- Clock
- Antifrost Mode
- Low battery indicator
- Temperature unit
- Room/setpoint temperature
- Program timeline indicator
- Program number
- Temporary override
- Eco Mode
- Comfort Mode
- Controlled device working status (e.g. boiler)
BUTTONS: - Increase
- Decrease
- Economic / Comfort Temperature
- LCD Backlight
- Temperature setpoint
- Weekly programming
- Time set
- Restore factory settings
Opening the case
T105 Wiring diagram
T105RF Wiring diagram
CHANGING THE COMMUNICATION CODE OF T105RF
Note: It is recommended to change the communication code to another than the factory to prevent other wireless devices interferences.
- Use DIP switches numbered 1-5 inside the thermostat to change the communication code
- Set DIP switches randomly – necessarily in the same position on the receiver as in the transmitter.
- Press the RESET button after the communication code changes.
Auto-adapt feature
Auto-adapt function is adjusting the operation of the heating device, so comfort temperature is reached on specific time. The auto-adapt feature is activated only when the room temperature is lower than the comfort temperature in the upcoming program. Temperature increasing time depends on the current temperature difference. The bigger the difference, the earlier function starts to work. Minimum auto-adapt feature startup time is 10 minutes before the programmed program, and a maximum – 50 minutes.
Setting Time
- Press button and then by button set the day of the week.
- Press button and then bybutton set the hour.
- Pressbutton and then use button to set the minutes.
Setting the economic / comfort temperature
- Press button, then by pressing select comfortable temperature ( icon on display) or economic temperature ( icon on display).
- Display will show currently set comfortable temperature. To change this temperature press.
- Press button or wait 10 sec. for temperature setting to be accepted.
Programs
- comfort temperature
- economic temperature
- There are 9 programs available. Programs 1-6 are factory programs.
Programs 7-9 can be defined by user.
Selection of factory (1-6) programs
- Press button and then by pressingchoose how to program the days of the week:
- each day separately (1, 2, 3, 4, 5, 6 or 7)
- business days and weekends (5 + 2)
- a whole week (7)
- Press button and then by pressing select program 1-6 for each day/days of the week.
- To confirm press button.
Choosing and Programming (7-9) user programs
- Press button and then by pressing choose how to program the days of the week:
- each day separately (1, 2, 3, 4, 5, 6 or 7)
- business days and weekends (5 + 2)
- whole week (7)
- Press the button and then by pressing select programs 7-9 for each day/days of the week.
- Pressbutton. Usebutton to change hours, use button to assign comfortable or economical temperatures for the specified hours.
Antifrost mode
Simultaneously hold down buttons to launch 7°C Antifrost Mode (for heating mode only). This mode will be active for the next program change. To exit from Antifrost Mode press any key on the thermostat.
Service parameters
To change service parameters use DIP switches numbered 1-3 located inside the thermostat.
SELECTING HEATING / COOLING MODE is changed by DIP switch#3. When switch is in the upper position (ON) – thermostat operates in heating mode, when switch is in the down position (OFF) – thermostat operates in cooling mode.
SPAN CONTROL – is changed by DIP switches #1 and #2. The parameters we can set are presented in the table below:
1 | 2 | Span |
ON | ON | 0,4°C |
OFF | ON | 0,8°C |
ON | OFF | 1,4°C |
OFF | OFF | 1,4°C |
IMPORTER:
QL CONTROLS Sp. z o.o. Sp. k.
ul. Rolna 4, 43-262 Kobielice
PRODUCER:
Salus Limited 6/F, Building 20E, Phase 3, Hong Kong Science Park, 20 Science Park East Avenue, Shatin, New Territories, Hong Kong
www.salus-controls.eu
SALUS Controls is a member of the Computime GroupMaintaining a policy of continuous product development SALUS Controls plc reserve the rightto change specification, design and materials of products listed in this brochure without prior notice
SALUS T105 Programmable Thermostat Quick Guide
The post SALUS T105 Programmable Thermostat Quick Guide appeared first on thermostat.guide.
source https://thermostat.guide/salus/salus-t105-programmable-thermostat-quick-guide/
No comments:
Post a Comment